ETC-2-AL controller
ETC-2-AL is an electronic device with an easy to read LED display used to measure carbon dioxide concentration in a building. Communication between the device and a CO2 sensor is digital and bidirectional what enables continuous control of its operation correctness.
ETC-2-AL supports some inaccurate situations that may occur during operation. In order to indicate them it has been equipped with a relay alarm output. An alarm is activated in the following situations:
- exceeding the set limit values of CO2 concentration,
- detection of CO2 measurement line damage,
- a failure in the device’s power supply,
- halting the process of monitoring of CO2 concentration,
- detection of irregularities in operation (e.g. an internal memory failure, keypad damage).
Supply voltage | 230 V, 50 Hz |
Class of anti-electric shock protection | II |
Relay alarm output | Umax: 24 V DC, Imax: 200 mA, Rin: 8,2 Ω |
Temperature of operation | 0 ÷ 40 °C |
Ambient relative humidity | 10 ÷ 90 % (non-condensing) |
Range of CO2 measurement | 400..10000 ppm |
Resolution of a setting and CO2 measurement | 100 ppm |
Accuracy of CO2 measurement | ±100 ppm +5% of measured value |
Settling time | about 300 s (rapid change of CO2 concentration from about 600 ppm to about 5000 ppm) |
Ingress protection class | IP55 |
Housing dimensions (height x width x thickness) | 114 x 128,5 x 57 mm |
Device weight(without a C02 sensor) | 0,33 kg |
Type of a cooperative CO2 sensor | CO2-10K |